FAIR PLAY 2000
Przedsiębiorstwo
"FAIR PLAY 2000"





medal
Zdobywca Złotego Medalu
"Eltarg 2002"

A A A

Switchgear SIVACON S8 with Rear Busbars Position (up to 7000 A)

VERSATILE AND SAFE –
TYPE-TESTED MODULES FOR POWER DISTRIBUTION


SIVACON Features

 

  • Type-tested standard modules (TTA)
  • 3- and 4-pole busbar system up to 6300 A
  • Rated peak withstand current Ipk up to 330 kA
  • Variable combination possibilities
  • Cable entry from the top, bottom or rear
  • Optional single or back-to-back assembly
  • Requirement-oriented separation of functional compartments from form 1 to form 4 (DIN EN 60439-1)
  • Withdrawable unit, removable unit, fixed-mounted and plug-in design can be combined in one section (universal installation system)



ALWAYS FLEXIBLE – SIVACON S8 ADAPTS TO YOUR REQUIREMENTS

  • Universal busbar position at the top of the cubicle
  • Withdrawable unit, removable unit, fixed-mounted and plug-in design can be combined in one section
  • User-oriented compartmentalization of functional compartments
  • Zero-maintenance busbar connections
- Main busbar connection in a separate compartment
- Partition between two cubicles




Frame and enclosure:
Accurate and Stable


The frame – including all supporting section elements – consists of stable screw-fastened sheet-steel profiles:

  • Circumferential hole rows with 25 mm hole grid for individual expansions
  • Patented door locking system for maximum personnel safety
  • Universal door hinge for easy door hinge adjustment
  • Door opening angle up to 125° (180° with standalone assembly)
  • Doors with double-bit fastener or pivoted lever lock
  • 100 mm or 200 mm base as add-on module
  • Roof plates with pressure relief
  • Frame heights optionally 2000mm or 2200mm,  100mm or 200mm base as add-on module


Surface Treatment
  • Galvanised frame parts and base
  • Galvanised cover
  • Powder-coated side panels, doors and base covers  RAL 7035, elements blue-green
Material

Frame and enclosure are manufactured from sheet steel in the following thicknesses:

Frame, base 2.5 mm
Cover 2,0 mm
Doors 2.0 mm
Partition, base plate 1.0 mm


Degrees of Protection to IEC 60529:

IP 30, IP 31, IP 41 ventilated
IP 54 non-ventilated

Wymiary celki (bez obudowy)

Wysokość celki
(mm)

Szerokość celki
(mm)

Głębokość celki
(mm)

2000

400, 600, 800, 1000, 1200

600/800

1000/1200

2200
(2000+ 200)

400, 600, 800, 1000, 1200

600/800

1000/1200


VARIABLE BUSBAR SYSTEM –
THE ANSWER TO A WIDE RANGE OF REQUIREMEN

Location of the main busbar

 

  • Optional busbar position at the top or rear.
  • Busbar systems for rated currents up to 7000 A
  • Rated peak withstand current (Ipk) up to 330 kA
  • Separation between busbar and equipment compartment
  • Two busbar systems can be integrated in the power distribution board
  • Shipping splits easily accessible from the front or top
  • Zero-maintenance busbar connections
  • Arc barrier for limitation of arcs to the individual cubicle (on request)
  • Isolated busbar systems agaist the short circuit (base-free design, on request)




CIRCUIT BREAKER SYSTEM
Compact and personnel safe


CIRCUIT BREAKER SYSTEM
Compact and personnel safe

Ease of operation, maximum benefits:
SENTRON 3WL

  • High safety thanks to type-tested standard modules (TTA)
  • Test and disconnected position with the door closed
  • Section dimensions matched to the circuit breaker size
    • 400mm width up to 1600A
    • 600mm width up to 3200A
    • 800mm width up to 4000A
    • 1000mm width up to 6300A
  • Optimum connection conditions for all nominal current ranges
  • Cable/busbar connection from the bottom/top
  • Type-tested SIVACON 8PS busbar trucking connections
  • Nominal current range from 630A to 6300A
  • Free selection of infeed direction without restriction of the technical data
  • High short-time current carryingcapacity for time-selective short-circuit protection up to 400msec guarantees safe operation of the unaffected system components
  • Optional short-circuit protection with timereduced selectivity control for very short delay times (50 msec), independent of the number of grading levels
  • LCD operating current display on the control panel – without additional current meter and transformer



With its compact design featuring a cubicle width of only 400 mm, SENTRON 3WL is perfectly suited for the nominal  current range up to 1600 A

 


EFFICIENT ASSEMBLY:
FIXED-MOUNTED 3NJ4 IN-LINE SYSTEM

Wymiary / budowa celek


Bezpiecznikowe listwy rozłącznikowe 3NJ4 Przyłącze kablowe od przodu
In-line cubicle with 3NJ4 in-line fuse switch disconnectors and rapid mounting kits for built-in installation devices

The cubicles for cable tap-offs in fixed-mounted system are equipped with switchable in-line fuse switch disconnectors, whose compact and modular design ensures an optimum efficiency of infrastructure applications.

  • High safety thanks to type-tested standard modules (TTA)
  • Cable feeders up to 630 A with/ without current measuring
  • Installation of up to 14 feeders per cubicle
  • De-energized fuse replacement
  • Doors optionally with/without cut-out
  • Optional installation of rapid mounting kits or freely installable equipment supports
  • Cubicle widths of 600 mm and 800 mm

PLUG-IN 3NJ6 IN-LINE SYSTEM
EASY ASSEMBLY AND SAFETY

Switching devices featuring an in-line system with an incoming plug-in contact represent an economic alternative to the withdrawable system and facilitate easy and fast  retrofitting and replacement works under operating  conditions thanks to their modular design. For these applications, SIVACON stands for high efficiency, safety and flexibility

  • High safety thanks to type-tested standard modules (TTA)
  • Switch disconnector with double interruption for cable feeders up to 630 A
  • Integrated current transformer (replaceable)
  • Manual or motor-driven operating mechanism
  • Accessories retrofi ttable by the customer
  • High packing density – up to 35 feeders per cubicle
  • Cable connection compartment with 400 mm or 600 mm width
  • Degree of protection up to IP41
  • Feeder replacement possible without disconnection of the power distribution board

 





3NJ6 switch disconnector with fuses

Plug-in busbar system, test finger-proof (IP20B)


UNIVERSAL INSTALLATION SYSTEM
SPACE FOR FLEXIBILITY



As many applications require a space-optimized assembly of the power distribution board, various installation systems must be integrated in a section. For these application cases, the SIVACON universal installation system offers high efficiency, safety and variability thanks to the combination of outgoing feeders in withdrawable unit design, removable unit design, fixed-mounted design and outgoing feeders in plug-in 3NJ6 in-line system. Furthermore, the withdrawable unit design offers the respective flexibility for frequently changing requirements such as changed motor ratings or connection of new consumers. In addition, this design also accounts for ergonomic aspects and facilitates easy and safe handling as well as short conversion times for maximum system availability.

The plug-in busbar system is arranged at the section rear. It is test-finger proof even without additional shutter to energized parts.

  • Arc-resistant embedding
  • Phase separation
  • 3- and 4-pole design
  • Test-fi nger proof (IP20B)
  • Tap openings in 50 mm module grid for standard withdrawable units and miniature withdrawable adapters

Optional

  • Shutters with double-action for standard withdrawable Units

Flexibility and safety for adjustments to changed requirements:

  • Easy conversion or retrofi tting of the withdrawable unit  compartments without disconnection of the section
  • No connection works in the withdrawable  unit compartment required
  • Connections for power and control cable in separate cable connection compartment
  • Front-side 400mm or 600mm wide cable connection compartment
  • Rear-side 600 mm wide cable connection compartment with 600 mm section width
  • Push-in clamp or screw connection for control cables

Quick-release lock or swivel covers/cover frames:

  • Innovative quick-release lock for easy and fast cover mounting
  • Swivel cover frame for fast commissioning and easy maintenance
Fixed-Mounted System with Front Covers

  • Innovative quick-release locking system for easy cover mounting
  • Swivel-mounted cover frame for improved commissioning and maintenance comfort

Technical data:

Normy i standardy

Aparatura łączeniowa i sterująca niskich napięć z badaniem typu (TTA)

Badanie reakcji na wewnętrzne zwarcia

Å‚ukowe

Ochrona przed porażeniem elektrycznym

IEC 60439-1

DIN EN 60439-1 (VDE 0660 Część 500)

IEC 61641, VDE 0660 Część 500, Suplement 2

(Ue up to 440 V, Icw up to 50 kA, t = 100 msec)

DIN EN 50274, VDE 0660 Część 514

Odległości bezpośrednie i pośrednie pomiędzy elementami czynnymi

Znamionowe napięcie impulsowe Uimp

8 kV / 12 kV

Kategoria przepięciowa

III / IV

Stopień zabrudzenia

3

Napięcie znamionowe izolacji (Ui)

Obwód główny

1000 V

Napięcie znamionowe pracy (Ue)

Obwód główny

do 690 V

Prąd znamionowy mostów szynowych (3-biegunowe i 4-biegunowe)

Główne szyny zbiorcze poziome

PrÄ…d znamionowy do 7000A

Znamionowy wytrzymywany prÄ…d udarowy (lpk) do 330kA

Znamionowy wytrzymywany prąd krótkotrwały (lcw) do 150kA, 1s

Szyny zbiorcze pionowe w technice wyłącznikowej

PrÄ…d znamionowy do 6300A

Znamionowy wytrzymywany prÄ…d udarowy (lpk) do 220kA

Znamionowy wytrzymywany prąd krótkotrwały (lcw) do 100kA, 1s

Pionowe mosty szynowe w technice montażu uniwersalnego i technice stacjonarnej

rÄ…d znamionowy do 1600A

Znamionowy wytrzymywany prÄ…d udarowy (lpk) do 143kA

Znamionowy wytrzymywany prąd krótkotrwały (lcw) do 65kA*, 1s

Szyny zbiorcze pionowe w technice listew wtykowych 3NJ6

PrÄ…d znamionowy do 2100A

Znamionowy wytrzymywany prÄ…d udarowy (lpk) do 110kA

Znamionowy wytrzymywany prąd krótkotrwały (lcw) do 50kA*, 1s

Prądy znamionowe urządzeń


3WL/3VL wyłączniki do 6300A

Odpływy kablowe do 630A

Separacja wewnętrzna

Formy 1 do 4b

IEC 60439-1, dział 7.7

VDE 0660 Część 500

Wykończenie powierzchni

Elementy szkieletu, cokół


Obudowa

cynkowane

Drzwi, ściany boczne, osłony cokołu

malowane proszkowo

Stopień ochrony

wg IEC 60529, EN 60529

IP30, IP31, IP40, IP41, IP54

Wymiary

Preferowane wymiary zgodne z DIN 41488

Wysokość 2000, 2200mm (z cokołem)

Szerokość: 400, 600, 800, 1000, 1200mm

Głębokość (przyścienna, wolnostojąca): 600, 800mm

Głębokość (double-front): 1000, 1200mm

* Znamionowy warunkowy prÄ…d zwarciowy lcc do 100kA