VERSATILE WITH SAFETY –
TYPE-TESTED COMPONENTS FOR POWER DISTRIBUTION
SIVACON Features:
- Type-tested standard modules (TTA)
- Standardized busbar position at the top of the cubicle
- 3- and 4-pole busbar system up to 7400 A
- Rated peak withstand current Ipk up to 375 kA
- Deep switchgear compartment for universal installation
- Modular structure of device compartments
- Single-front and back-to-back installation
- Cable lead-in from above or below
- Cable connection from the front or rear
Â
Â
Always flexible –
Sivacon adapts to your requirements
- Standard horizontal busbar position at the top of the cubicle
- Any components can be installed in the device compartments regardless of the busbar position and cubicle depth
- Requirement-oriented compartmentalization of functional units (Form 1 to Form 4 according to IEC 60439-1)
- Deep device compartments
Â
Optimum adaptation to space conditions:
- Wall-mounted or free-standing
- Cables and busbars may be connected optionally from above or below
- Cabling compartments front- or rear-located
- Good accessibility of busbars
FRAME AND ENCLOSURE –
DIMENSIONALLY ACCURATE AND STABLE
Â
|
- All-round perforation rows with a 25-mm hole grid for individual installation
- Flexible door system for all requirements
- Door opening angle up to 180°
- Spring-loaded locks reliably prevent doors from opening unintentionally
- Pressure-relief top covers
Surface Treatment: Optionally powder-coated, wet-painted or sendzimir-galvanized Material: Frame and enclosure are manufactured from sheet steel in the following thicknesses: Frame: 2.5 mm Enclosure: 2.0 mm Degrees of Protection to IEC 60529 IP 30, IP 31, IP 40, IP41, IP 42 naturally ventilated IP 40, IP 54 unventilated
Â
|
Â
Â
VARIABLE BUSBAR SYSTEM –
THE ANSWER TO DIVERSE REQUIREMENTS
Â
|
- Busbar position at top
- Busbar system for rated currents up to 7400 A
- User-oriented gradation of rated currents
- Rated peak withstand current Ipk up to 375 kA
- Separation of the busbar compartment from the device compartment
- Transport unit joints easily accessible from above
- Arc barriers for limiting the effects of the arcing fault
Â
|
Â
Â
CIRCUIT-BREAKER DESIGN
COMPACT, RELIABLE AND USER-FRIENDLY
Compact and Reliable |
Przyjazna z 3 WL |
- High degree of safety due to type tested standard modules (TTA)
- Test and disconnected positions with door closed
- Circuit breakers integrated in separate compartments, each equipped with a separate door
- Optimum connection conditions for every rated current range
- Cable connection from above or below
|
Siemens 3W. fixed-mounted and withdrawable circuit breakers are used for the rated current range from 630 to 6300 A. This means:
- Free choice of the supply direction without any restrictions in terms of technical data
- High short-time current-carrying capacity for time-graded shortcircuit protection up to 400 ms assures reliable operation of sections of the switchboard not affected by a short-circuit
- Short-circuit protection with shorttime grading control (ZSS) for very brief delay times (50 ms), irrespective of the grading level
- LCD operating current indication in the control console (without ammeters and current transformers)
- Indication and operation when the door is closed
|
Â
FIXED-MOUNTED DESIGN –
ECONOMICAL, RELIABLE AND VARIABLE
|
Modular Cable Feeders The modular cable feeders enable efficient installation, above all whenever operation-specific changes or adaptations are necessary.
- Molded-case circuit breakers or fuseswitch isconnectors can be fitted as required
- Free combination of cable feeders within one cubicle
- Continuously adjustable mounting plates for a standard front plane
- Cable feeders with and without current measurement
Â
|
Â
|
Cable feeders in compartment design
The compartment design with its individual sub-section for every circuit breaker offers increased active safety for installation and personnel protection.
- Individual sub-sections with doors for each circuit breaker
- Circuit breaker 3VL with or without plug-in socket
- High form of internal separation up to Form 4 Type 7 acc. to BS EN 60439 (gland box per functional unit)
- Optimum connection conditions inthe rear cable connection compartment
|
Â
Switchable In-Line Fuse-Switch Disconnectors The in-line fuse-switch disconnectors make for optimum packing density thanks to their compact design and their modular structure.
- Cable feeders up to 630 A with/without current metering
- 25 feeders can be installed in each cubicle
- Dead-state fuse replacement
|
|
Â
IN-LINE PLUG-IN DESIGN 3NJ6 –
PLUGGED-IN SWIFTLY, ALWAYS SAFE
- High level of safety by virtue of type-tested standard modules (TTA)
- Supply-side plug-in contacts enable quick replacement
- In-line type switching devices for cable feeders up to 630 A available in
the following designs:
- Fuse module with fuses
- Fuse-switch disconnectors (single-break)
- Fuse-switch disconnectors (double-break)
- Switch disconnectors
- High packing density (up to 34 feeders per cubicle)
- Dead-state fuse replacement
- Protection against electric shock from plug-on bus system 400 and 600 mm wide cable connection compartment
- Degree of protection up to IP 40
- Possibility of replacing a feeder without having to shut down the system
|
|
Â
CUBICLE FOR CUSTOMISED SOLUTIONS –
PLENTY OF SPACE FOR FLEXIBILITY
Â
|
- 3- and 4-pole vertical distribution busbars
- Rated currents up to 1200 A
- Rated short-time withstand current up to Icw 65 kA
- Cubicle-length doors or compartment doors
- Compartmentalization
- Various installation components
|
Â
TECHNICAL DATA –
AT A GLANCE
Â